Multiple Range Compact Heatmeter
The most advanced technology for the market
our development challenge:

INTEGRAL MK MultiSensor
for nominal flows of Qn 1,0m³/h or 2,5m³/h

MultiSensor MutliSensor
logoams



dar



dqs
    • PTB class C approval, horizontal and vertical
    • multi range meter for at least 2 nominal flows per nominal diameter
      Qn 1,0 for flows Qn 0,5 - 0,6 - 0,75 - 1,0 m³/h
      Qn 2,5 for flows Qn 1,5 - 2,5 m³/h
    • improved starting flow due to no-side-effect impeller wheel scanning combined hard metal-sapphire bearings
    • the thermally uncoupled calculator assures longer battery and LCD display lifetimes
    • easy to service measurment capsule design
    • removable calculator assures optimal assembling
    The Multi-Fuction-Display allows to call up the following measurment values to control and adjust the heating system: (19 values - here some of them:
    • Heat
    • Volume
    • Flow
    • Temperature difference
    • Flow and Backflow temperature
    • Thermal power
    • Display test
    • Heat, Volume, etc. on preprogrammed days
    • Volume of two connected water meters
    • M-BUS compatible
    The INTEGRAL MK MultiSensor is fully compatible with the ALLMESS-Measuring Capsule System. The uncomplicated mounting of the INTEGRAL MK MultiSensor into the MK Measuring Capsule System, which has been proven since 1985, simplifies post-calibration, thus reducing related servicing and exchange costs. Thanks to the new design, the calculator can also be swivelled by 90° and installed in any position. The INTEGRAL MK MultiSensor can be installed even under the most difficult conditions. The calculator can be removed and installed separately (Wall mounting).

    FIELD OF APPLICATION
    Due to the wide dynamic range, the amount of types could be drastically reduced. Thus, the type Qn 1,5 m³/h, which was so far normally used for homes, can in general be replaced by type Qn 1,0m³/h. This means simplification of planning, calculations and stocks for our customers!

    OPTIONS
    The INTEGRAL MK MultiSensor is available either with a remote reading output (M-BUS) or with an energy repetition output (FA). The remote reading allows for central reading of several meters with the M-BUS System (EC-normed). Inquiry and computer assisted evaluation of the neasurment values is performed over an inductive coupling box.

    FUNCTION PRINCIPLES:

    CALCULATOR
    Heat calculation is performed by a microcontroller integrated within the calculator, which is thermally uncoupled from the flow sensor system. This reduces self-unloading of the battery and increases the lifetime of the LCD display. Volume impulse resolution of the impeller wheel scanning surpasses that of the present equipment by far. Next to the evaluated heat, the LCD display can indicate volume, flow, temperature difference, flow and backflow temperatures and thermal power upon request. The heat meter is indipendent of any power supply system and can thus be installed universally at any place of the backflow.
    The INTEGRAL MK MultiSensor is insensitive towards dirt and conductivity modifications of heating medium. A second oscillating circuit assures automatic zero compensation. Due to this, neither axial play of the impeller wheel nor surrounding temperature have influence on measurement accuracy. Operation of the INTEGRAL MK MultiSensor is securely protected against HF emission and magnetic disturbances. The impeller wheel must drive no mechanical gearing of any kind. Thus, its starting limit below 3l/h is substantially lower than that of mechanical-magnetic gearings. The low inertia of the impeller wheel allows to cover a very extensive dynamic range of heat and volume measurements.
    TEMPERATURE MEASUREMENT
    Temperature measurement is carried out by means of two computer-paired platinum resistence thermometers Pt100. The characteristic lines of the thermometers correspond to DIN IEC 751 (class B). The termal coefficient k is continously adapted to the temperature range. Measurment is carried out directly in the heating medium or over sensor pockets. Direct measurement thus allows for shorter response times of the temperature sensors.

trasmissione VOLUME MEASUREMENT
The damping modulation principle is based on the modification of an electric oscillator circuit consisting of a capacitor and a coil, in which oscillations are generated at very short intervals. A damping disc fixed to the impeller wheel is subvided into a metallic and non metallic sector. These sectors cause different damping od the oscillations generated by the capacitor or the coil - an effect which allows for non magnetic and no-side-effect scanning and evaluation of the impeller wheel rotation.

The Multi-Fuction-Display allows to call up 19 values - here some of the most important
Display Multifunzionale
The damping modulation principle
Interno del MultiSensor





SPLIT HEATMETER


MEGACONTROL
CF50

for nominal flows up to Qn 250 m³/h

megacontrol CF50
click on the immage for better view


under construction
still under constructuion.....



For more information (info@oilcontrol.it)

[